Next: Ideal Transformer
Up: Chapter 3: AC Circuit
Previous: Quality Factor, Peak Frequency
All loads of the power plant can be modeled by a two-terminal network of
passive elements (resistors, inductors, capacitors, without any energy
sources) with complex impedance
where
.
As most of the loads are inductive (e.g., electric motors), i.e.,
, the phase angle
of the impedance is always positive. Assume the
input voltage to the load network is:
then the current through the power transmission line and load can be found as:
where
is the effective current.
The instantaneous power of the load is defined as
Here
(*
)
In particular, consider the average of
and
over a period
:
It is seen that the instantaneous power is composed of two components: the
first term
representing energy dissipation, and
the second term
representing energy
not dissipated but stored in the system. Instantaneous
can be
both positive (for energy consumed by the load) and negative (for energy
released by the load).
The average power over a period
is:
- Apparent Power:
;
- Real power:
This is the first term (non-zero) of the average power expression,
which is consumed by the load (dissipated, converted to heat);
- Reactive Power:
This is the second term (zero) of the average power expression,
which is not consumed but converted back and forth between the
energy source and the energy storing elements (inductors and capacitors).
The definitions of real power
and reactive
power
above suggest that the power
can
be treated a complex variable:
i.e.,
Substituting
into the equation, we have
Comparing the two expressions for
above, we get:
Now we see that the real power
is the power dissipated by
the resistive component
of the load, while the reactive power
is stored in and released from the reactive component
(inductiv
or capacitive
) of the load.
Improvement of Power Factor
The Power factor is defined as
which not only measures the phase difference between the voltage and
current in the system, but also determines the ratio between the real
power (
) transmitted from power generation
to power consumption; and the reative power (
)
not contributing to power transmission. To increase the efficiency of
the power transmission system, i.e., to deliver as much real power
to the consumer as needed while minimizing the current (limited by the
power transmission system), it is desirable to maximize the power
factor
by reducing
. As most loads are inductive
(due to the coils in electric motors), the power factor can be reduced
by using the shunt capacitor to cancel the inductance in the system.
Example: Assume the impedance of the inductive load is
with phase
. Find
of
the shunt capacitor so that
and
.
The most straight forward way is to add a shunt capacitor in series
with the inductive load, so that the inductance can be canceled by the
capacitance:
Solving this we get
. However, note that now the overall
load becomes a series RCL circuit at resonance with quality factor:
and the magnitude of the voltage across the inductor and the capacitor
is
times that across the resistor:
When
,
could be very large and the high
voltages across
and
may be harmful.
As an alternative, the shunt capacitor
can be added in parallel
to the load, now the overall load becomes
For the new phase angle
to be zero, we need to have
which can be solved for
to get
Note that another benefit of this method is that the required
is
smaller than the series approach.
Sometimes an unrealistically large capacitance is needed if the power
factor has to be increased to 1 (
), while it is actually
acceptable for the improved power factor to be less than 1, e.g., 0.9.
In this case, the phase angle of the load is
Solving this equation we can obtain a
. As now we have
i.e.,
we get an even smaller capacitance
more practically implementable.
Next: Ideal Transformer
Up: Chapter 3: AC Circuit
Previous: Quality Factor, Peak Frequency
Ruye Wang
2008-03-23